Product Details:
Payment & Shipping Terms:
|
Product Name: | Transmission Line Test System | Input Power Source: | Three Phase AC380V±10% |
---|---|---|---|
Maximum Output Voltage: | AC300V Accuracy:1% | Maximum Output Current: | 5A |
Output Signal Frequency: | 42.5Hz/57.5Hz;45Hz/55Hz;47.5Hz/52.5Hz;50Hz/50Hz | Dimension: | 535 Mm×435 Mm×360mm(not Including Wheel) |
Weight: | 61kg | Interference Voltage: | Longitudinal Induced Voltage After Connect To Testing Power: <350V |
Interference Current: | When Line Ends Are Short Circuited To Earth:<40A | Temperature: | - 15℃ ~ +40℃ |
Relative Humidity: | <90% | ||
High Light: | AC300V Transmission Line Parameter Test System,DFT Transmission Line Parameter Tester |
High Voltage Different Frequency Transmission Line Parameter Test System
Product introduction
Features
Input power source | Three phase AC380V±10% | ||
Maximum output voltage |
AC300V accuracy:1% | ||
Maximum output current |
5A | ||
Output signal frequency |
42.5Hz/57.5Hz;45Hz/55Hz;47.5Hz/52.5Hz;50Hz/50Hz | ||
Measuring range |
positive sequence capacitance, zero sequence capacitance, coupling capacitance |
positive sequence impedance, zero sequence impedance, mutual inductive impedance |
Impedance angle |
0.1-50μF | 0.5-400Ω | 0°~360° | |
Resolution | 0.01μF | 0.01Ω | 0.01° |
Accuracy | 0.1μF~1μF: ±3%±0.05μF | 0.5Ω~1Ω:±3%±0.05Ω | ±0.2°(voltage>1.0V) |
1μF~50μF时±1.5%±0.03μF | 01Ω~400Ω:±3%±0.03Ω | ±0.3°(voltage>0.2~1.0V) | |
Dimension | 535 mm×435 mm×360mm(not including wheel)weight: 61kg | ||
Anti-interference Parameter |
Interference voltage: longitudinal induced voltage after connect to testing power: <350V | ||
Interference current: when line ends are short circuited to earth:<40A | |||
Can accurately make measurements when the output signal and the interference signal is 1:10 | |||
Working environment | Temperature - 15℃ ~ +40℃ relative humidity <90% |
Contact Person: Emma
Tel: 86-17396104357
Fax: 86-27-65526007