Product Details:
Payment & Shipping Terms:
|
Working Voltage: | AC 220V±10% DC12.6V 4000mAH | Powe: | 50w |
---|---|---|---|
Accuracy: | 0.2 | Pressure Display Resolution: | 0.001Mpa |
Humidity: | ≤90%RH | Operation: | Rotary Mouse |
High Light: | protection relay test equipment,protective relay tester |
Circuit Breaker SF6 Density Relay 50W Auto Calibration Tester
Features:
1. Microcomputer to detect and control the density relay, high precision, good repeatability and strong reliability.
2. Large LCD, rotating mouse, easy operation, beautiful interface, all parameters and status at a glance
3. Automatically finish the conversion between pressure measurement and 20℃, thereby finish the dynamic automatic compensation between pressure and temperature. And display the pressure of the measured environment, the equivalent pressure under 20℃, temperature
4. All the testing process is automatic, without manual intervention.
5. Printing and intelligent data analysis function
6. Can store 50 groups of testing results at the same time, data will not lose when power off, historical data can be reviewed and printed at any time.
7. No need thermostatic chamber during the test
8. Equipped with transition joint, can do field test for most of the density relay without disassembly
9. Will not waste SF6 during the test, with low test cost, without pollution to environment.
10. Can on line modify system clock
11. Can on line modify system pressure on site
12. Reliable by using advanced imported core components
13. Can test on group alarm signal, two groups atresia signal simultaneously
14. This product is portable device, easy and reliable to use, it is the ideal equipment for SF6 density tests.
15. With large capacity Li-battery inside, continuous work time 8 hours, charging time less than 4 hours
Parameter:
1. Working Voltage: AC 220V±10% DC12.6V 4000mAH
2. Power: 50w
3. Accuracy: 0.2
4. Pressure display resolution: 0.001Mpa
5. Pressure measurement range: 0~1.0MPa
6. Temperature display resolution: 0.1℃
7. Temperature measurement range: -20℃~80℃
8. Humidity: ≤90%RH
9. Test objects: Single alarm / single-atresia / single-alarm & single-atresia / single-alarm & dual-atresia
10. Display: 320*240 Graphics Dot Matrix monochrome LCD
11. Operation: rotary mouse
12. Printer: High-speed micro printer, print method: report type
13. Storage Capacity: Can save 50 test results at the same time
14. Dimensions: main machine 365X300X220(mm) accessories box: 400x370x200mm
15. SF6 density display: The pressure of the measured environment, the equivalent pressure under 20℃
16. Net Weight: 8KG
Contact Person: Nie Qi
Tel: 86-18507140027