Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17362949750
Product Details
Place of Origin: CHINA
Brand Name: GDZX
Certification: IDO9001
Model Number: DDG
Payment & Shipping Terms
Minimum Order Quantity: 1
Packaging Details: carton
Payment Terms: L/C,T/T,Western Union,
Current Output: |
500A 1000A 2000A |
Open Voltage: |
5V 6V 10V |
Primary Voltage: |
200V |
Primary Current: |
30A |
Secondary Voltage: |
6V |
Secondary Current: |
1000A |
Current Output: |
500A 1000A 2000A |
Open Voltage: |
5V 6V 10V |
Primary Voltage: |
200V |
Primary Current: |
30A |
Secondary Voltage: |
6V |
Secondary Current: |
1000A |
The DDG Primary Current Injection Test Set is a high-current generator instrument designed for protective device inspection, secondary circuit current testing, current transformer testing, circuit breaker testing, and other current-loaded and temperature-rise tests. It is widely used in power plants, power distribution stations, electrical plants, scientific research facilities, and laboratories.
| Type | Capacity (kVA) | Primary V1 | Primary A1 | Secondary V2 | Secondary A2 | Dimensions L×W×H (mm) | Weight (kg) | Structure |
|---|---|---|---|---|---|---|---|---|
| 500A | 3 | 200 | 15 | 6 | 500 | 430×338×550 | 48 | Integrated |
| 1000A | 6 | 200 | 30 | 6 | 1000 | 500×380×600 | 80 | Integrated |
| 2000A | 12 | 220 | 50 | 6 | 2000 | 550×420×700 / 400×520×800 | 65 / 45 | Separated |
| 2500A | 15 | 380 | 39.5 | 6 | 2500 | 600×430×790 / 580×480×820 | 85 / 65 | Separated |
| 3000A | 18 | 380 | 55 | 6 | 3000 | 620×440×800 | 160 | Separated |
| 4000A | 24 | 380 | 63 | 6 | 4000 | 640×450×820 / 300×500×500 | 105 / 85 | Separated |
| 5000A | 30 | 380 | 79 | 6 | 5000 | 600×430×900 / 300×500×500 | 145 / 135 | Separated |
| 6000A | 36 | 380 | 95 | 6 | 6000 | 600×430×900 / 300×500×500 | 150 / 140 | Separated |
| 8000A | 48 | 380 | 126 | 6 | 8000 | 600×450×950 / 350×550×550 | 180 | Separated |
| 10000A | 60 | 380 | 158 | 6 | 10000 | 800×600×1100 / 380×550×600 | 200 | Separated |
| 20000A | 60 | 380 | 158 | 6 | 20000 | 800×600×1100 / 380×550×600 | 240 | Separated |
For separated structures, dimensions and weights are listed for the control unit and the current generator unit respectively.