Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17396104357
Product Details
Place of Origin: Hubei, China
Brand Name: GDZX
Model Number: ZX-BZK
Payment & Shipping Terms
Minimum Order Quantity: 1 Set
Price: $1,500.00 - $3,500.00 / Sets
Packaging Details: Carton or wooden box
Delivery Time: 7~10 work days
Payment Terms: L/C, D/A, D/P, T/T
Supply Ability: 1200 Set/Sets per Year
Product Name: |
Short-circuit Impedance Test |
Power Supply: |
AC220V±10%,50Hz±1Hz |
Measurement Accuracy: |
Voltage, Current 0.2% |
Voltage Measurement Range: |
AC 3V-300V |
Current Measuring Range: |
AC 0.2A-20A |
Working Temperature: |
-10℃--50℃ |
Product Name: |
Short-circuit Impedance Test |
Power Supply: |
AC220V±10%,50Hz±1Hz |
Measurement Accuracy: |
Voltage, Current 0.2% |
Voltage Measurement Range: |
AC 3V-300V |
Current Measuring Range: |
AC 0.2A-20A |
Working Temperature: |
-10℃--50℃ |
3V - 300V Transformer Winding Deformation Tester Short Circuit Impedance Test
Low-voltage short-circuit impedance test is to the most direct way to check the deformation of the winding after transformer suffered from short-circuit current or mechanical collision during transportation and installation, the test is important to help determine whether the transformer can be put into operation, and whether disintegration is necessary for inspection. ZX-BZK transformer short-circuit impedance tester comes with adjustable power output, particularly suitable for 110kV and above main transformer on site measurement.
Features
1. With switching power supply, just one time wiring connection can finish measurement for all the windings, no matter it is single phase transformer or three phase transformer
2. Single phase measurement mode. To three phase transformers, each phase short circuit impedance, reactance, inductance can be obtained automatically after three times boosting.
3. Adopts phase locking technology, synchronize sampling AC signal which ensures accuracy
4. current, voltage and power, frequency can be measured at the same time
5. Support external connection with CT/PT to extend measuring range
6. With memory to store data, with printer
7. LCD display with operation menu, data can be read clearly even under direct sunlight
Main Technique Parameters
Measurement accuracy | Voltage, current 0.2% |
Power | COSφ>0.1 0.5%; COSφ≤0.1 1.0% |
Impedance | COSφ>0.1 0.5%; COSφ≤0.1 1.0% |
Voltage measurement range | AC 3V-300V |
Internal power supply output range | Voltage 0-250V, current 0-10A |
Current measuring range | AC 0.2A-20A |
Working temperature | -10℃--50℃ |
Humidity | 0-80% |
Power supply | AC220V±10%,50Hz±1Hz |
Dimension | 360*220*150mm |
Net Weight |
About 5kg |