Product Details:
Payment & Shipping Terms:
|
Product Name: | Microcomputer Control Universal Relay Tester | Power Supply: | AC 220V±10%,50/60Hz |
---|---|---|---|
Environment Temperature: | -10℃~+50℃ | Weight: | 22kg |
Dimension: | 400*300*180mm3 | Warranty: | 1 Year |
High Light: | protection relay test equipment,protective relay test set |
u Standard 4 voltage 3 current channels output, voltage 120V/phase, current 40A/phase, 3 phases in parallel: up to 120A; the fourth phase voltage Ux is for multiple functions
u Rotating knob to operate, preheating unnecessary, total group test can be done thorugh all kinds of transient, permanent, transferring failures simulation.
u Can connect to PC to wrok via software, convenient to scan various protection setting values, real time save testing results, display vector graphics, draw fault wave and print reports
u Suitable for complex check requiring high degree automation: service power fast switching test, spare power automatic switching test, line protection reclosing test etc.
u Rich amount of switching contacts
u Large LCD screen
u Self-protection: reasonable design of heat dissipation structure, reliable and perfect protection and power soft start, self-diagnosis and block function.
u Independent DC power output
u Cost effective
ITEM/MODEL | ZX-702 | ||
AC current output | Output accuracy | 0.5 class | |
Phase current output (RMS) | 0~40A | ||
Three parallel phase current output (RMS) | 0~120A | ||
Phase current allowed long running value (RMS) | 10A | ||
Phase current maximum power output | 420VA | ||
Three parallel phase current maximum power output | 900VA | ||
Three parallel phase current maximum work time | 10s | ||
Frequency range (base wave) | 20~1000Hz | ||
Harmonic order | 1~20th | ||
DC current output | Output accuracy | 0.5 class | |
Current output | 0 ~ ± 10A / each phase | ||
0 ~ ± 30 A / three parallel | |||
Maximum output of load voltage | 20V | ||
AC voltage output | Output accuracy | 0.5 class | |
Phase voltage output (RMS) | 0 ~ 120v | ||
Line voltage output (RMS) | 0 ~ 240v | ||
Phase voltage/line voltage power output | 80VA/100VA | ||
Frequency range (base wave) | 20 ~ 1000Hz | ||
Harmonic order | 1~20th | ||
Direct voltage output | Phase voltage output amplitude | 0 ~ +160v | |
Line voltage output amplitude | 0 ~ + 320v | ||
Phase voltage/line voltage power output | 70VA/140VA | ||
Switching contacts and time measurement | Binary input | 7channels | |
Dead contact:1~20mA, 24V Electric potential contact connection to “0”:0~+6V;“1”:+11 V~+250V |
|||
Binary output | 2 pairs | ||
DC:220V/0.2A AC:220V/0.5A | |||
Time measurement Range | 0.1ms~9999s, accuracy:0.1mS | ||
Others | Size | 400×300×180mm³ | |
Net Weight | 22kg | ||
Power Supply Voltage | AC 220V±10%,50/60Hz | ||
environment temperature | -10℃~+50℃ |