Universal operation step
Connect test loop correctly according to wiring diagram and related requirements. Set on-site warning marks for test. Set various test parameters correctly.
Click “Automatic test” after entering into interface of Figure 2 or 4. Click “Start test” after entering into interface of Figure 5. Then the tuning, voltage rising, timekeeping and voltage desending can be carried out automatically.
![]()
Figure 1
The interfaces will be shown in following: Tuning
![]()
Figure 2
![]()
Figure 3
Timekeeping:
![]()
Figure 4
Voltage descending:
![]()
Figure 5
If there is some protective action during the test, there will be related interfaces shown in Figure 10 and 11.
Over-voltage protection:
![]()
Figure 6
Flashover protection:
![]()
Figure 7
Click “Manual test” after entering into the interface of Figure 2 or 4; Click “Start test” after entering into the interface of Figure 12. Then, the manual/ semi-automatic frequency modulation and manual voltage rising can be carried out.
![]()
Figure 8
![]()
Figure 9
Semi-automatic test: the automatic tuning will be carried out by clicking “Tuning”; Rise voltage manually by clicking “Rise voltage” and “Descend voltage” after finishing tuning. Notice: the “Frequency stepping adjustment” and “Voltage stepping adjustment” should be set in advance before clicking “Tuning”, or the tuning will not be carried out automatically.
![]()
Figure 10
Manual test: the manual tuning will be carried out by clicking “Rise frequency” and “Descend frequency”; Rise voltage manually by clicking “Rise voltage” and “Descend voltage” after finishing tuning. Notice: the “Frequency stepping adjustment” and “Voltage stepping adjustment” should be set in advance before clicking “Rise frequency”, “Descend frequency”, “Rise voltage” and “Descend voltage”; or the “Rise frequency”, “Descend frequency”, “Rise voltage” or “Descend voltage” shall not be clicked.
![]()
Figure 11
5.5.3. Data inquiry and output test result
Enter material interface by clicking “File management” after entering into the interface of Figure 2; then records for all previous tests can be consulted, shown in Figure 16.
![]()
Figure 12
The test value can be saved only by clicking “Save data” in automatic test or manual test. The real-time data shall not be saved for not clicking “Save data”. After inserting U flash disk into USB interface, the historical data can be saved in U flash disk by pulling out of U flash disk after 1 min after clicking “Send historical data”. The historical data can be generated into “Excel” file on computer through the self-programmed software of our company.