Product Details:
Payment & Shipping Terms:
|
Power Supply: | AC 220V±10%(customized) | Frequency: | 50Hz/60Hz±1% |
---|---|---|---|
Usage: | Oil Dielectric Loss Tester | Ambient Temperature: | 0 ℃ ~ 40 ℃ |
Dimension: | 420*380*385mm | Capacitance: | 5pF ~ 200pF |
DC Resistivity: | 2.5 MΩm ~ 20 TΩm | ||
High Light: | oil breakdown voltage tester,transformer oil breakdown voltage test kit |
This is used for measuring dielectric dissipation factor and DC resistivity of insulating oil and other insulating liquids, applied in heavy interference site such as power plants or power substations. It can also be used in laboratory for high accurate test.
The device is whole in one designed: Including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits. It adopts full digital technology and all of the intelligent automatic measurement, so that the operator without professional training will be able to use it proficiently.
1. Power supply: AC 220V±10%(customized)
2. Frequency: 50Hz/60Hz±1%
3. Measuring range:
Capacitance: 5pF ~ 200pF
Relative permittivity 1.000 to 30.000
Dielectric loss factor of 0.00001 to 100
DC resistivity 2.5 MΩm ~ 20 TΩm
4. Measurement accuracy:
Capacitance: ± (1% of reading + 0.5pF)
The relative permittivity of ± 1% of reading
Dielectric loss factor ± (1% reading +0.0001)
DC resistivity ± 10% of reading
5. Resolution:
a) capacitance 0.01pF
b) relative permittivity 0.001
c) Dielectric loss factor 0.00001
6. Measured temperature range: 0 ~ 125 ℃
7. Temperature measurement error: ± 0.5 ℃
8. AC test voltage: 500 ~ 2200V continuously adjustable, frequency 50Hz
9. The DC test voltage: 0 ~ 500V continuously adjustable
10. Power consumption: 100W
11. Ambient temperature: 0 ℃ ~ 40 ℃
12. Relative humidity: <75%
13. Dimension: 500×360×420mm
14. Net Weight: 22KG
Contact Person: Nie Qi
Tel: 86-18507140027