Send Message

Wuhan GDZX Power Equipment Co., Ltd sales@gdzxdl.com 86--17396104357

Wuhan GDZX Power Equipment Co., Ltd Company Profile
products
Home > products > Transformer Testing Equipment > Partial Discharge Detection Transformer Testing Equipment Switchgear PD Tester

Partial Discharge Detection Transformer Testing Equipment Switchgear PD Tester

Product Details

Place of Origin: CHINA

Brand Name: GDZX

Certification: ISO9001

Model Number: ZXPD-100K

Payment & Shipping Terms

Minimum Order Quantity: 1

Packaging Details: wooden box

Payment Terms: L/C, T/T, Western Union, MoneyGram

Get Best Price
Product Details
Highlight:

current transformer test set

,

transformer testing machine

Sensor:
UA TEV Sensor
Test Band:
UA 40~200KHz
Measuring Range:
UA:-90~80dB
UHF:
00~2000MHz -80~10dBm
Sensor:
UA TEV Sensor
Test Band:
UA 40~200KHz
Measuring Range:
UA:-90~80dB
UHF:
00~2000MHz -80~10dBm
Product Description

Switchgear Partial Discharge Detection Switchgear PD Tester

 

Features

1. Scope of application: non contact detection method 

2. The sensor configuration

1) Standard: UA TEV sensor

2) Transformer testing sensing network,GIS UHF sensor, HV cable sensor for options, customizable

3. Detection principle: UA TEV UHF

4. software function

1) Continuous detection of UA TEV UHF signals for detection of PD

2) Real time display the tested signal trend for intuitive judgment on the development of PD signal.

3) data storage in the field

5. Instrument index

1) Screen display: High contrast 3.5 inch TFT color screen

2) Data storage:1000 sets of testing results

 

Technical Indicators

1. Detection band

1) UA:40~200KHz

2) TEV: 3~100MHz

3) UHF:00~2000MHz

2. measuring range

1) UA:-90~80dB

2) TEV:-80~10dBm

3) UHF:-80~10dBm

3. sensitivity:minimum 10pC (depending on the distance between the sensor and the discharge source).

4. sensor

1) UA sensor:20~200(kHz)

2) TEV:3~100MHz

5. UHF sensor:300~2000(MHz),have directional reception characteristics.

1) Working power supply: built-in 8.4V lithium battery can Continue work for 8 hours

2) Power Supply:input:100-240VAC,output:8.4V/3A,Charge time 3~4hours.

3) outline dimension:230×120×55mm

4) Instrument Net weight:0.7kg

5) Operation temperature:-25℃~45℃

6) Storage temperature:-35℃~60℃

 

Partial Discharge Detection Transformer Testing Equipment Switchgear PD Tester 0