Home > products > CT PT Analyzer > Multi Function CT PT Analyzer Characteristic Tester , Transformer Test Equipment

Multi Function CT PT Analyzer Characteristic Tester , Transformer Test Equipment

Product Details

Place of Origin: Hubei, China

Brand Name: GDZX

Model Number: ZXHQ-A

Payment & Shipping Terms

Minimum Order Quantity: 1

Price: $2,500.00 - $4,000.00 Set/Sets

Packaging Details: Carton or Wooden box

Delivery Time: 7~15 work days

Payment Terms: L/C, T/T

Supply Ability: 1200 Set/Sets per Year

Get Best Price
Product Details
Highlight:

ct pt test set

,

current transformer test set

Product Name:
CT PT Characteristic Tester High Accuracy Transformer Test Equipment
Power Supply:
AC220V±10% ,50Hz
Output:
0-2500V, 0-1000A
Work Environment:
-10℃ ~ 40℃, ≤90%RH,≤1000m
Product Name:
CT PT Characteristic Tester High Accuracy Transformer Test Equipment
Power Supply:
AC220V±10% ,50Hz
Output:
0-2500V, 0-1000A
Work Environment:
-10℃ ~ 40℃, ≤90%RH,≤1000m
Product Description

 

 

 

Functions

CT( Protection and measuring type) PT
exciting characteristic curve exciting characteristic curve
Auto calculate Knee point Auto calculate Knee point
5%, 10% error curve, auto Turns ratio
Turns ratio Polarity
Ratio error Ratio error
Phase error Phase error
Polarity C withstand
Primary injection Secondary load
AC withstand Secondary winding
Secondary load Degaussing
Secondary winding  
Degaussing  

 

Work power supply AC220V±10% ,50Hz
Output

0~2500Vrms, 5Arms(20A peak)

Remark:0~5A(RMS), >5A~20A(Calculation)

Current output 0~1000A
Excitation accuracy ≤0.5%(0.2%*reading+0.3%*range)
Secondary winding resistance test Range 0.1~300Ω
Accuracy ≤0.5%(0.2%*rdg+0.3%*range)
Secondary load test Range 5~1000VA
Accuracy ≤0.5%(0.2%*rdg+0.3%*range)±0.1VA
Phase error Accuracy ±4min
Resolution 0.1min
Ratio error Accuracy 0.05%
CT Ratio test Range ≤25000A/5A(5000A/1A)
Accuracy ≤0.5%
PT ratio test Range ≤500KV
Accuracy ≤0.5%
Work environment -10℃ ~ 40℃, ≤90%RH,≤1000m
Tester dimension and G.W.

410mm × 260mm × 340mm, 30Kg

 

 

Multi Function CT PT Analyzer Characteristic Tester , Transformer Test Equipment 0

Multi Function CT PT Analyzer Characteristic Tester , Transformer Test Equipment 1