Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
News
Wuhan GDZX Power Equipment Co., Ltd
Home ProductsCT PT Analyzer

China Manufacturer IEC Standards CT PT Testing Equipment Test Accuracy 0.05

China Wuhan GDZX Power Equipment Co., Ltd certification
China Wuhan GDZX Power Equipment Co., Ltd certification
Product is good by performance, yes it is good for xxxxxx market.

—— Mr Dudani

Your product received very good, we will order one more piece

—— JS

You are very nice company. Thanks for your hospitality i spend very informative in your office

—— Yousri

Good for whatever the product or service, you got my trust through this deal.

—— Rahul

Very reliable supplier and partner, solving my question with great patience and perfession.

—— Gaurav

I'm Online Chat Now

China Manufacturer IEC Standards CT PT Testing Equipment Test Accuracy 0.05

China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05
China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05

Large Image :  China Manufacturer IEC Standards CT PT Testing Equipment Test Accuracy 0.05

Product Details:
Place of Origin: CHINA
Brand Name: GDZX
Certification: ISO9001
Model Number: ZXHQ-Y
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: 7990usd -12000usd
Packaging Details: carton
Payment Terms: L/C, T/T, Western Union, MoneyGram
Supply Ability: 50pcs/month
Detailed Product Description
Features: Report Test Without Nameplate Power supply: AC220V±10%,50Hz/60Hz±10%
Power output: 0.1~125V (AC) Ratio: Test Error 0.05%
Power Output: 300VA Knee Voltage: Test Range 0-45kV
High Light:

current transformer test set

,

ct pt testing equipment

                                  IEC standards CT PT Analyzer Instrument transformer Test Equipment


Functions

1. The instrument is used for below CT tests

2. Excitation characteristic test
3. Turn ratio detection
4. Ratio error and angular difference calibration
5. Polarity calibration
6. Secondary winding resistance measurement
7. Secondary load measurement
8. 5 % and 10% deviation curve measurement
9. CT transient characteristics test and analysis
10. Automatically detects CT nameplates
11. Inflection point voltage/current, accuracy limit factor, safety factor, second time constants, residual magnetism

12. factor, accuracy, saturated and unsaturated inductance, inflexion electromotive force, limiting e.m.f. area factor etc.
13. Current transformer iron core hysteresis loop measurement.

And following PT test:

PT Turn ratio and phase angle difference detection.
PT polarity calibration
PT secondary winding resistance measurement
Secondary load measurement

 

China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 0

 

Applications

CT nameplates parameters calibration
Calibrating parameters when CT connect to current load.
Analyzing relay protection device according to the CT transient characteristics.
PT nameplates parameters calibration.
PT secondary load calibration.

Parameters:

1. Test standards: IEC60044-1, IEC60044-2, IEC60044-5, IEC60044-6, C57.13

2. Power supply: AC220V±10%,50Hz/60Hz±10%

3. Power output: 0.1~125V (AC)

4. Current output: 0.001~5A(RMS)

5. Power output:300VA

6. Maximum knee voltage measurement: 45kv

7. Current measurement:

Range:0~10A (auto ranging 0.1/0.4/2/10A)

Error <±0.1%+0.01%FS

8. Voltage measurement:

range:0~200 V (auto ranging 1V/10V/70V/200V)

Error < ±0.1%+0.01%FS

9. Turns ratio measurement:

Range :1~30000,

1~2000 error<0.05%

2000~5000 error<0.1%

5000~30000 error<0.2%

10. Phase measurement: error:±2min,resolution:0.01min

11. Secondary winding resistance measurement:

Range:0~8kΩ (auto ranging 2ohm/20ohm/80ohm /800ohm /8kohm)

Error< 0.2%RDG+0.02%FS

Maximum resolution:0.1mΩ

12. Temperature measurement:-50~100 Celsius degree, error<3 Celsius degree

13. CT Secondary load:

Range 0~160ohm (auto ranging: 2ohm/20ohm/80ohm/160ohm)

Error <0.2%RDG+0.02%FS

Maximum resolution 0.001ohm

14. PT Secondary load:

Range 0~80kohm (auto ranging: 800ohm/8kohm/80kohm)

Error <0.2%RDG+0.02%FS

Maximum resolution: 0.1ohm

15. PT Turns ratio measurement:

Range :1~30000,

1~5000 error<0.2%

5000~30000 error<0.5%

16. Saved data groups:>1000groups

17. Operating condition: Temperature:-10℃~50℃, moist:≤90%

18. Size: 485mm×356mm×183mm

19. Weight: <15Kg

 

China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 1

 


China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 2

China Manufacturer IEC Standards CT PT Testing Equipment  Test Accuracy 0.05 3

Contact Details
Wuhan GDZX Power Equipment Co., Ltd

Contact Person: nieqi007

Tel: +8618507140027

Send your inquiry directly to us (0 / 3000)